Unavailable
Nominal voltage 200
240 V
Power factor λ 0.95/0.85
Nominal output power 52 W
Input voltage AC 198
264 V
Mains frequency 50
60 Hz
Nominal output voltage 27
54 V
Device power loss 3.5 W
ECG efficiency 83 %
Nominal current 0.11 A
Inrush current 24 A
Max. no. of ECGs on circuit breaker 10 A 17
Galvanic isolation primary/secondary 3.75 kV
▼ see full specification ▼
Electrical data
Nominal voltage
200
240 V
Power factor λ
0.95/0.85
Nominal output power
52 W
Input voltage AC
198
264 V
Mains frequency
50
60 Hz
Nominal output voltage
27
54 V
Device power loss
3.5 W
ECG efficiency
83 %
Nominal current
0.11 A
Inrush current
24 A
Max. no. of ECGs on circuit breaker 10 A
17
Galvanic isolation primary/secondary
3.75 kV
Max. no. of ECGs on circuit breaker 16 A
28
Surge capability (L-N)
1 kV
Nominal output current
250 / 300 / 350 mA
Input voltage DC
176
276 V
Dimensions & weight
Length
103.0 mm
Width
67.0 mm
Height
29.5 mm
Mounting hole spacing, length
94.0 mm
Mounting hole spacing, width
58.0 mm
Cable cross-section, input side
0.2
1.5 mm²
Product weight
165.00 g
Cable cross-section, output side
0.2
1.5 mm²
Wire preparation length, input side
8.5
9.5 mm
Lifespan
ECG lifetime
50000 h
Capabilities
Dimmable
No
Suitable for fixtures with prot. class
I / II
Overheating protection
Automatic reversible
Max. cable length to lamp/LED module
2.0 m
No-load proof
Yes
Overload protection
Automatic reversible
Short-circuit protection
Automatic reversible
NTC input
No
Certificates & standards
Approval marks approval
ENEC 10 / VDE / EMC / EL / CE
Standards
Acc. to EN 61347-1/Acc. to EN 61347-2-13/Acc. to EN 55015/Acc. to EN 61547/Acc. to EN 61000-3-2/Acc. to EN 62384
Type of protection
IP20
Colors & materials
Casing material
Plastic
Temperatures
Ambient temperature range
-25
+50 °C
Maximum temperature at tc test point
75 °C
Temperature range at storage
-25
85 °C
Max.housing temperature in case of fault
110 °C
Product benefits
Versatile scope of application due to output power range of up to 50 W
Safety requirement due to overload, overtemperature, Hot Plug protection
High efficiency and reliability
Areas of application
Installation in emergency lighting systems according to IEC 61347-2-3, appendix J
Suitable for installation in emergency lighting systems according to EN 60598-2-22
Suitable for central battery systems according to EN 50172
Suitable for use in luminaires with flexible current setting (Tri-Tap)
Suitable for use in emergency lighting systems (DC capable)
Suitable for indoor SELV equivalent installations
Suitable for luminaires of protection classes I and II
Product features
Supply voltage: 220…240 V
Line frequency: 0 Hz, 50 Hz…60 Hz
Line voltage: 198…264 V
Safety according to EN 61347-1, 61347-2-3, 61347-2-13, 62384
Module operation according to EN 60929
RI suppression according to EN 55015:2007+A1:2007/CDN
Line harmonics according to EN 61000-3-2
Immunity according to EN 61547
Lifetime: up to 100,000 h (temperature at Tc = 65 °C, max. 10 % failure rate)
Recommended also
Rated 5.0 /5
based on 1 customer reviews
31,16
€
OPTOTRONIC FIT
Rated 5.0 /5
based on 1 customer reviews
https://www.electrico24.eu/uploads/assortment_images/a-16535-117225.jpg
Power Equipment / Power Supplies
Osram https://www.electrico24.eu/uploads/producer_logos/d83bdb510944b8ad8743f3d191f9d801.png
OPTOTRONIC FIT
75.94 PLN
available
Recommended
Rated 5.0 /5
based on 1 customer reviews
6,45
€
Rated 5.0 /5
based on 1 customer reviews
from 48,16
€
Rated 5.0 /5
based on 1 customer reviews
192,05
€
Rated 5.0 /5
based on 1 customer reviews
from 103,64
€
Rated 5.0 /5
based on 1 customer reviews
11,02
€
Rated 5.0 /5
based on 1 customer reviews
332,83
€
Wondering how to select a light source for luminaire? Below is a list of popular light sources of Osram and Philips with base information and the light source indication.
Fluorescent Linear and Circular
Base
Power
(W) Luminous flux
(lm) OSRAM PHILIPS Fluorescent Linear T5 (T16)
G5
8
400
Basic T5Short
L 8W
TL MiniStandard
TL Mini 8W 14
200... read more »